Brand Name : GINRI
Model Number : SVR100
Certification : CE
Place of Origin : CHINA
MOQ : 10Pcs
Payment Terms : L/C, T/T, Western Union,Paypal
Supply Ability : 20000Pcs per month
Delivery Time : 5-8 working days
Packaging Details : 1 relay in individual box
Size : 80*43*54mm
contact capacity : 6a 250vac
mounting : din rail
reset mode : manual/automatic/automatic with power-on delay
Single Phase Over Under Voltage Relay SVR1000 AC/DC Supply LCD Protector
The Features of SVR10000
-- Powered by the measuring circuit
-- Built-in LCD and keypad afford a precise,digital setting
-- Compact modular 43mm housing
-- Adjustable over- and undervoltage threshold
-- Independent adjustable delay time for overvoltage, undervoltage
-- 1 CO & 1NC contacts
-- Fault recording with last 3 faults
♦ Protective Functions
-- Overvoltage
-- Undervoltage
♦ Typical Applications
• Pumps • Fans
• Blowers • Motors
• Compressors
♦ Approvals
• CE • CCC
♦ Technical data
Model | SVR1000/D12 | SVR1000/AD48 | SVR1000/AD220 | ||
Measuring circuit | A1+,A2- | ||||
Rated voltage | DC 12V | AC/DC 24~48V,50/60Hz | AC/DC 110~240V,50/60Hz | ||
Monitoring functions | overvolatege, undervoltage | ||||
Overvoltage setting range | DC 9.0~18.0V adjustable | AC/DC 20.0~80.0V adjustable | AC/DC 50.0~300V adjustable | ||
Undervoltage setting range | DC 9.0~18.0V adjustable | AC/DC 20.0~80.0V adjustable | AC/DC 50.0~300V adjustable | ||
Voltage hysteresis | 0.1~6.0V adjustable | 0.1~30.0V adjustable | 1.0~90.0V adjustable | ||
Delay time for overvoltage and undervoltage | 0.1-999s adjustable | ||||
Reset mode | Manual/ Automatic/Automatic with power-on delay | ||||
Delay time for reset | 0.1-999s adjustable | ||||
Indicators | LCD indicating voltage,operationand fault status | ||||
Output contacts | 1 CO & 1NC | ||||
Contact capacity | 6A ,250VAC | ||||
Dimensions (H x W x D) | 80×43×54mm | ||||
Mounting | DIN rail |
Single-phase over-voltage and under-voltage protector (also known as voltage monitor, over-voltage and under-voltage protector, etc.) is mainly used for AC 50/60Hz, rated voltage below 250V, industrial single-phase 220V and other voltage levels for various fault detection, for single phase The input power supply voltage is too high and the voltage is too low to provide relay protection. It is an indispensable protection product for the normal working voltage of the maintenance equipment in the operation of industrial equipment.
![]() |